The 100% question bank provides Fire service operators Examination questions 、 Fire service operators Test prediction questions 、 Fire service operators The real exam question 、 Fire service operators Certificate examination question bank, etc , Provide online questions and brush questions , Online mock exam , Help you pass the exam easily .

 

1. The fire alarm controller only receives the fire alarm information , What information will be displayed on the LCD , Which of the following statements is true .(  )

A、 Alarm device location information

B、 Fire alarm information

C、 Fault information

D、 Fire alarm time

answer :A-B-D

analysis : The fire alarm controller only receives the fire alarm information , The LCD screen will display the position information of the alarm equipment ; Fire alarm information ; Fire alarm time .

132、 After the fire alarm controller receives the fire alarm signal , Which of the following statements is true .(  )

A、 Make a sound 、 Optical alarm signal

B、 The broadcast controller starts

C、 The fire alarm indicator shall be on

D、 Fire detector location , Record the fire alarm time

answer :A-C-D

analysis : After the fire alarm controller receives the fire alarm signal , Will make a sound 、 Optical alarm signal , The fire alarm indicator shall be on , And display and record the position of fire detector 、 Alarm time .

133、 Which of the following belongs to the functional inspection of the fire alarm controller :(  )

A、 Fire alarm self checking function

B、 Main and standby power switching function

C、 Fault alarm function

D、 Fire priority function

answer :A-B-C-D

134、 Different brands 、 Products from different manufacturers , The programming methods of the fire alarm controller program are different . Generally, it can be divided into .(  )

A、 And logic programming

B、 Field programming

C、 Background programming

D、 Or a logic programming

answer :B-C

analysis : In general , The programming method of fire alarm controller program can be divided into field programming 、 There are two kinds of background programming .

 

135、 The fire alarm controller can be divided into... According to the monitoring area (  ).

A、 Centralized

B、 Regional

C、 Concentrated area type

D、 Control center alarm system

answer :A-B-D

analysis : The fire alarm controller can be divided into centralized type according to the monitoring area 、 Regional 、 Control center alarm system .

135、 The operation status information of building fire-fighting facilities in the smoke control system includes :(  )

A、 Manual operation of the system 、 Automatic working state

B、 Working state of power supply for smoke control and smoke exhaust fan

C、 Fan 、 Electric fire damper 、 Electric smoke exhaust fire damper 、 Normally closed air supply outlet 、 Normal working state and action state of smoke exhaust valve staircase 、 Residual pressure information of anterior chamber and shared anterior chamber

D、 Electric smoke exhaust window 、 Normal working state and action state of electric smoke retaining vertical wall .

E、 answer :A-B-C-E

analysis : In building fire-fighting facilities , The operation status information of smoke control system includes :1、 Manual operation of the system 、 Automatic working state ;2、 Working state of power supply for smoke control and smoke exhaust fan ;3、 Fan 、 Electric fire damper 、 Electric smoke exhaust fire damper 、 Normally closed air supply outlet 、 The normal working state and action state of the smoke exhaust valve ;4、 Electric smoke exhaust window 、 Normal working state and action state of electric smoke retaining vertical wall .

136、 The operation status information of building fire-fighting facilities in the fire hydrant system includes :(  )

A、 Working state of fire pump power supply

B、 Start of fire pump 、 Stop state and fault state

C、 Fire water tank ( pool ) The water level 、 Pipe network pressure information

D、 Alarm information of fire hydrant button

E、 Manual operation of fire pump 、 Automatic status .

answer :A-B-C-D

analysis : In building fire-fighting facilities , The operation status information of the fire hydrant system includes :1、 Working state of fire pump power supply ;2、 Start of fire pump 、 Stop state and fault state ;3、 Fire water tank ( pool ) The water level 、 Pipe network pressure information ;4、 Alarm information of fire hydrant button

137、 The pre action system consists of (  ) Other components .

A、 Open sprinkler

B、 Water supply facilities

C、 Pre action valve block

D、 Inflatable equipment

E、 Fire detector

answer :B-C-D-E

analysis : The pre action system consists of a closed sprinkler 、 Water supply facilities 、 Pre action valve block 、 Inflatable equipment 、 Fire detector, etc .

138、 Press... On the fire alarm controller " Self inspection " key , All on the controller (  ) All shall be able to enter the self inspection state , After the self-test is completed , It shall be able to automatically exit the self inspection state .

A、 Indicator light

B、 Alarm sound

C、 Fire emergency broadcast

D、 Liquid crystal display

E、 Graphic display device

answer :A-B-D

analysis : Press down " Self inspection " key , All indicators on the controller 、 Alarm sound 、 All LCD shall be able to enter the self inspection state , After the self-test is completed , It shall be able to automatically exit the self inspection state .

139、 Linkage control and feedback signal of the system at each stage of the startup and discharge of the gas fire extinguishing device , It shall be fed back to the fire linkage controller . The linkage feedback signal of the system shall include the following contents (  ).

A、 The alarm signal of the fire detector directly connected to the gas fire extinguishing controller

B、 Select the action signal of the valve

C、 Action signal of pressure switch

D、 Pipe network pressure signal

E、 Start stop signal of the system .

answer :A-B-C

analysis : The linkage feedback signals of the device startup of the gas fire extinguishing system and the spraying at each stage include the following contents :1、 The alarm signal of the fire detector directly connected to the gas fire extinguishing controller ;2、 Select the action signal of the valve ;3、 Action signal of pressure switch .

141、 The layout of equipment in the fire control room shall comply with the following provisions (  ).

A、 Operating distance in front of the equipment face plate , When arranged in a single row, it shall not be less than 1.5m; In case of double row arrangement, it shall not be less than 3m

B、 On the side where the person on duty often works , The distance from the equipment panel to the wall shall not be less than 3m

C、 The maintenance distance behind the equipment panel should not be less than lm

D、 The arrangement length of equipment face plate is greater than 4m when , Its two ends shall be set with a width not less than lm The passage of

E、 Fire control room shared with other weak current systems of the building , Fire fighting equipment shall be set centrally , There shall be a clear gap with other equipment

answer :B-C-D-E

analysis : Operating distance in front of the equipment face plate , When arranged in a single row, it shall not be less than 1.5m; In case of double row arrangement, it shall not be less than 2m.